Value
Text display
Description
CM210
Current Outside Temperature of the zone
-60 °C - 60 °C
CM230
Outside Temperature average long time per zone
-60 °C - 60 °C
CM260
Measure of the room sensor temperature of the zone
-60 °C - 60 °C
GM001
Actual fan RPM
0 Rpm - 8500 Rpm
GM002
Actual fan RPM setpoint
0 Rpm - 8500 Rpm
GM004
Gas valve 1
0 = Open
1 = Closed
GM005
Gas valve 2
0 = Open
1 = Closed
GM006
Gas Pressure Switch status
0 = Open
1 = Closed
GM008
Actual flame current measured
0 µA - 25 µA
GM010
Available power in % of maximum
0 % - 100 %
GM012
Release signal for the CU
0 = No
1 = Yes
GM015
Valve Proving System switch open / closed
0 = Open
1 = Closed
GM044
Possible reason for Controlled Stop
0 = None
1 = Central Heating Blocking
2 = Domestic Hot Water Blocking
3 = Wait for burner start
4 = Flow temperature above absolute max
5 = Flow temperature above start temperature
6 = Heatexchanger temperature above start
temperature
7 = Average flow temperature above start temperature
8 = Flow temperature above max setpoint
9 = Temperature difference too high
10 = Flow temperature above stop temperature
11 = Average flow temperature above stop
temperature
NM001
Cascade system flow temperature
-60 °C - 125 °C
PM002
External winning Central Heating setpoint
0 °C - 125 °C
9.4.3
Status and sub-status
Tab.35 Status numbers
Status
0
Standby
1
Heat Demand
2
Burner Start
3
Burning Central heating
4
Burning Dhw
5
Burner Stop
6
Pump Post Run
7
Cooling Active
8
Controlled Stop
9
Blocking Mode