10 Maintenance
10.1 General
The boiler does not require a lot of maintenance. Nevertheless, the boiler
must be inspected and maintained periodically. To determine the best time
for servicing, the boiler is equipped with an automatic service message.
The control unit determines when this service message appears. Depend
ing on boiler use, the first service message appears no later than 3 years
after installation of the boiler.
Caution
Maintenance operations must be completed by a qualified in
staller.
During inspection or maintenance work, always replace all gas
kets of the disassembled parts.
Replace defective or worn parts with original spare parts.
An annual inspection is mandatory.
10.2 Maintenance message
The boiler display will clearly indicate that a service is required at the ap
propriate time.
See
Manual for the control panel
Use the automatic service message for preventive maintenance, to keep
faults to a minimum. The service messages show which service kit must
be used. These service kits contain all parts and gaskets that are required
for the relevant service. These service kits (A, B or C), put together by
Remeha , are available from your spare parts supplier.
Important
A service message must be followed up within 2 months. There
fore, call your installer as soon as possible.
If the iSense modulating controller is connected to the boiler,
this maintenance message can also be forwarded to the iSense.
Consult the manual for the regulator.
Caution
Reset the maintenance message following every service.
10.2.1 Resetting the service messages
A service message on the boiler display must be reset by a qualified in
staller within two months after the indicated maintenance service has been
carried out using the relevant service set and after this has been entered
in the checklist. Proceed as follows:
1. Perform the service with the specified service kit (A, B or C).
2. Note the service in the corresponding checklist.
See
Appendix, page 75
3. Reset the service message.
See
Manual for the control panel
10 Maintenance
7625116 - v.04 - 17012017
55