3 Technical specifications
3.1
Homologations
3.1.1
Certifications
Tab.1
Certifications
CE identification number
PIN 0063CQ3781
NOx class
6 (EN 15502-1)
Type of connection
B
23P
, B
33
C
13
, C
33
, C
43
, C
53
, C
63
, C
83
, C
93
3.1.2
Unit categories
Tab.2
Unit categories
Country
Category
Gas type
Connection pressure (mbar)
Great Britain
II
2H3B/P
G20 (H gas)
G30/G31 (butane/propane)
20
30-50
3.1.3
Directives
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines speci
fied in this manual.
3.1.4
Factory test
Before leaving the factory, each boiler is optimally set and tested for:
Electrical safety.
Adjustment of (O
2
/CO
2
).
Water tightness.
Gas tightness.
Parameter setting.
3.2
Technical data
Tab.3
General
Quinta Ace
160
Nominal output (Pn) for central heating operation (80°C/60°C)
min. - max.
(1)
kW
31.5 - 152.1
152.1
Nominal output (Pn) for central heating operation (50°C/30°C)
min. - max.
(1)
kW
34.7 - 161.6
161.6
Nominal input (Qn) for central heating operation (Hi) G20 (H gas)
min. - max.
(1)
kW
32.0 - 156.0
156.0
Nominal input (Qn) for central heating operation (Hi) G31 (Propane)
min. - max.
kW
40.0 - 156.0
Nominal input (Qn) for central heating operation (Hs) G20 (H gas)
min. - max.
(1)
kW
35.6 - 173.3
173.3