Caution
Changing the factory settings may adversely affect the operation
of the boiler.
9.4
Reading out measured values
9.4.1
Reading out current values (counters)
Tab.33 Counters
Value
Text display
Description
AC001
Number of hours that the appliance has been on mains
power
0 Hours - 65534 Hours
AC002
Number of hours that the appliance has been
producing energy since last service
0 Hours - 131068 Hours
AC003
Number of hours since the previous servicing of the
appliance
24 Hours - 131068 Hours
AC004
Number of generator startings since the previous
servicing.
0 - 65534
AC026
Counter that shows the number of pump running hours 0 Hours - 65534 Hours
AC027
Counter that shows the number of pump starts
0 - 65534
DC001
Total power consumption used by Domestic Hot Water 0 kW - 4294967295 kW
DC004
Number of burner starts for Domestic Hot Water
0 - 65534
DC005
Number of burner hours in Domestic Hot Water
0 Hours - 65534 Hours
GC007
Number of failed starts
0 - 65534
PC002
Total number of burner starts. For heating and
domestic hot water
0 - 65534
PC003
Total number of burner hours. For heating and
domestic hot water
0 Hours - 65534 Hours
PC004
Number of burner flame loss
0 - 65534
9.4.2
Reading out current values (signals)
Tab.34 Signals
Value
Text display
Description
AM001
Is the appliance currently in domestic hot water
production mode.
0 = Off
1 = On
AM010
The current pump speed
0 % - 100 %
AM011
Is service currently required?
0 = No
1 = Yes
AM012
Current main status of the appliance.
See
Status and sub-status, page 51
AM014
Current sub status of the appliance.
See
Status and sub-status, page 51
AM015
Is the pump running?
0 = Inactive
1 = Active
AM016
Flow temperature of appliance.
-25 °C - 150 °C
AM017
The temperature of heat exchanger
-25 °C - 150 °C
9 Settings
7625116 - v.04 - 17012017
49