Value
Text display
Description
AM018
Return temperature of appliance. The temperature of
the water entering the appliance.
-25 °C - 150 °C
AM019
Water pressure of the primary circuit.
0 bar - 12 bar
AM022
On / Off heat demand
0 = Off
1 = On
AM024
Actual relative power of the appliance
0 % - 100 %
AM027
Instantaneous outside temperature
-60 °C - 60 °C
AM028
Value of the 0 to 10 Volt input. Meaning is dependant
on the current input function setting.
0 V - 25 V
AM033
Next service indication
0 = None
1 = A
2 = B
3 = C
4 = Custom
AM036
Temperature of the exhaust gas leaving the appliance
0 °C - 250 °C
AM037
Status of the three way valve
0 = CH
1 = DHW
AM040
Temperature used for hot water control algorithms.
0 °C - 100 °C
AM044
Number of sensors supported by the device
0 - 255
AM045
Is a water pressure sensor present?
0 = No
1 = Yes
AM091
Seasonal mode active (summer / winter)
0 = Winter
1 = Winter system frost protection acitve
2 = Summer neutral band
3 = Summer
AM101
Internal system flow temperature setpoint
0 °C - 125 °C
AP078
Outside sensor detected in the application
0 = No
1 = Yes
CM030
Measure of the Room temperature of the zone
-60 °C - 60 °C
CM120
Zone Current Mode
0 = Scheduling
1 = Manual
2 = Antifrost
3 = Temporary
CM130
Current activity of the zone
0 = Anti frost
1 = Reduced
2 = Comfort
3 = Anti legionella
CM140
Open Therm Controller is connected to the zone
0 = No
1 = Yes
CM150
State of On Off Heat demand per zone
0 = No
1 = Yes
CM160
Presense of modulating heat demand per zone
0 = No
1 = Yes
CM170
Zone Open Therm smart power function is avaible
0 = No
1 = Yes
CM180
Presense of Room Unit in this zone
0 = No
1 = Yes
CM190
Wished room temperature setpoint of the zone
-60 °C - 60 °C
CM200
Displaying current operating mode of the zone
0 = Standby
1 = Heating
2 = Cooling
9 Settings
50