Manual - TC.P Quadro
Commissioning
2016-08-05
70/330
V04.52
3
Function test
Condition for the function test:
Mains voltage switched on.
Connected load.
Vary the procedure depending on which interface you use.
With analogue interface X105
The control signal VOLTAGE_ON can be applied from a pos-
sible input device (e.g. PLC, 12 V
DC
power supply) via the in-
terface X105. Set values can also be defined via this inter-
face.
For further information see chapter 3.3.3.3, page 75.
With the HMI (option)
Set values can be defined via a rotary switch on the related
menu.
Further information from chapter 6.3.4, page 148.
With the RS-232 interface
In combination with a PC and the TopControl application the
set values can be defined on the <CONTROL> tab and the
device switched on.
For further information see chapter 6.4.7.1, page 184.
Check the output voltage or current to ensure it matches the set values.
Please note that, depending on the configuration of ramp functions, the
set values specified may in some circumstances only be reached after
the related ramp functions/time have been completed.
Error-free state
After you have set the set values, the following occurs in the error-free
state:
The output is switched on and regulated to the related set value
defined.
The device is in the state: RUNNING,
One CONTROL LED illuminates depending on the controller that
is providing the limiting.
CV for voltage controller
CC for current controller
CP for power controller
Error state
In the error state a flashing error code is output on the front via the
CONTROL LED.
For further information see chapter 9.1, from 264.
If there is no output voltage at the device, check the interlock safety cir-
cuit using the related dummy plugs.
For further information see chapter 3.3.1, page 71.