Manual - TC.P Quadro
Commissioning
2016-08-05
69/330
V04.52
3
Self-test r
eports status: “OK”.
READY light emitting diode (green) illuminates continuously.
The device is ready.
State machine changes to the “READY” state.
For further information see chapter 3.3.6, page 78.
Self-
test reports status: “Error”.
Error light emitting diode (red) illuminates or flashes.
Flashing code on the ERROR light emitting diode indicates the
reason for the error.
For further information see chapter 9.1, from page 264.
State machine changes to the “ERROR” state.
For further information see chapter 3.3.6, page 78.
If the state machine remains in the “ERROR” state after a re-
peated start attempt, look for the reasons for the error using the
“TopControl” application and take the necessary corrective
measures.
Parameterisation
If possible do not make any changes to the factory settings, as the fac-
tory settings take into account your needs, the operation foreseen and
your individual applications in the majority of cases.
If you nevertheless need to make application-specific settings, you can
make them using the TopControl application from your PC.
However, prior to changing the settings we recommend undertaking the
function test described in the following and only then changing the set-
tings. In particular for monitoring values, ramp functions or controller
settings.