Input Module Number and Input Signal Name Fields
Simple CT Temperature Scaling Setup
described below.
Input module
number
Displays the input module number for which the si
mple “CT,
Temperature” scaling parameters are being configured.
Input signal
name
Displays the user-assigned name of the
signal for which the simple “CT,
Temperature” scaling parameters are being configured.
Winding Rise Parameters
Simple CT Temperature Scaling Setup
described below.
Oil
Temperature
Adder
Allows you to select one of the available RTD Input Modules. The
selected RTD Input Module will be the liquid temperature measurement
that is added to the winding curve simulation, for example, top oil
temperature.
Winding Rise
Temperature
Allows you to set the number of degrees that the winding temperature will
be over the oil temperature (delta T) at nominal load for the transformer.
You can calculate this parameter from the transformer heat run test
reports by subtracting the oil temperature at nominal loading from the
winding temperature at nominal loading. If you cannot obtain the heat run
report, contact the transformer manufacturer for these values.
Current
Factor
Displays the value measured at the clamp-on CT sensor of the 509ITM at
nominal loading of the transformer.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......