67
www.qualitrolcorp.com
Custom Scaling
The configuration parameters in this section of the
change the scaling of the process input signal. Custom Scaling is not available if the
is set to a "Logic Switch" or "AC/DC Input". For
“Temperature” input
modules, for example,
“RTDs”, “Ambient”, and “CT, Temperature” using custom scaling
switches the values from Celsius to Fahrenheit. The fields in this section are described
below.
Use Custom
Scaling
Indicates that custom scaling is defined for the input signal. If the check
box is checked, you must specify three additional parameters for the
input:
•
Custom Units Label
field allows the user up to three characters for a
unit of measure, for example, ppm, RH, %.
•
Low-End Value
field is the scaled minimum value for the
corresponding minimum input value.
•
High-End Value
field is the scaled maximum value for the
corresponding maximum input value.
Custom Units
Label
If the
Use Custom Scaling
field is checked, the 509ITM uses this label
instead of the default label defined by the
. This
label can consist of up to three alphanumeric characters.
Low-End and
High-End
Scaling
Values
Provide the custom values corresponding to the indicated low-end and
high-end values for the selected module type. The 509ITM translates the
input signal into the alternate monitors using the low- and high-end
values provided.
Example:
You have a Dissolved Gas Monitor with 0 - 1 mA representing
a 0 - 2000 PPM scale. Using a 0 - 1 mA input module, set:
•
Low-End Scaling Value
field to “mA = 0”
•
High-End Scaling Value
field to
“1 ma = 2000”
•
Custom Units Label
field to
“PPM”
An input of 0.4 mA would appear as 800 PPM on the display.
Low-End and High-End Scaling Values
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......