129
www.qualitrolcorp.com
Actuate alarm
(Yes / No)
Enables (Yes) / Disables (No) the actuation of the alarm relay if the
inrush current exceeds the setpoint threshold limits.
Motor Actuations
This section of the
High Priority LTC Alarm Setup
window
includes the fields described
below.
Motor
actuations
setpoint
Allows you to enter the setpoint value that actuates the alarm relay if the
number of motor actuation counts equals or exceeds the value.
Present
counts
Displays the total number of motor actuation counts detected up to this
point in time.
You can view the number and leave it as is, or you can reset or preset
the count by entering a new number.
Actuate alarm
(Yes / No)
Enables (Yes) / Disables (No) the actuation of the alarm relay if the
number of motor actuation counts exceeds the setpoint value.
Motor Actuation Time
This section of the
High Priority LTC Alarm Setup
window
includes the fields described
below.
Last actuation
time
Displays the measured time of the last tap position motor actuation.
Use this value as a guide for selecting a maximum setpoint time for the
motor actuation to occur before actuating the alarm relay.
Setpoint
Allows you to enter the maximum setpoint time for the motor actuation to
occur before actuating the alarm relay.
Actuate alarm
(Yes / No)
Enables (Yes) / Disables (No) the actuation of the alarm relay if the motor
actuation time exceeds the setpoint value.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......