Forecast Override Setpoint:
Enter a setpoint for the first column
of the relay matrix when the
Threshold Value
is exceeded for the
specified number of hours.
2. Click [Load].
Example:
If the ambient temperature exceeds 30
C for at least 12 hours
over the previous 120 hours, the effective setpoint for the first column is
50
C.
Cooling Equipment Exerciser
The Cooling Equipment Exerciser actuates the relay for a set period of time at a specified
interval of days. This feature allows you to exercise a seldom-used fan circuit to prevent
rust, lubricate bearings, and to keep wildlife from nesting in fan cages.
includes the fields described below.
Important:
Do not enable the exerciser for any relay that controls a trip function.
Enabled /
Disabled
Allows you to enable or disable this feature.
Exercise time
Allows you to set the number of minutes that the relay remains actuated
when the cycle time is reached. The range is 0 - 59 minutes.
Cycle time
Allows you to set the amount of time between each exerciser actuation.
The range is 0 - 30 days.
Start time
Allows you to set the time of day that the exerciser starts to run once the
cycle time is completed. The range is 0 - 23, in military time format.
Low
temperature
module #
If the equipment exerciser is used to exercise cooling pumps (not fans)
an ambient input module number may be entered here to prevent
transformer damage caused by the movement of oil at cold temperatures
(electro stratification).
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......