The Input
Channel Calibration
window displays.
Important:
Variations in the individual resistor values require that you calibrate every
position of the Tap Position Resistor Bridge, starting with the lowest tap
position. For this reason, the transformer should be offline during the
calibration.
13. Take the transformer offline.
14. In the
Set input signal to
field, enter the lowest tap position.
15. Click [Next].