162
www.qualitrolcorp.com
The
Calibrator - Signal Selection
window displays with the radio button for
Input 1
selected.
4.
Click the radio button for the input module that displays “Potentiometer.” In the example
above, this is
Input 3
.
CAUTION:
Check again that you have selected the correct input module before
proceeding. Calibrating any other input module could erase the system’s
calibration values and cause the 509ITM to malfunction.
5. Click [Calibrate].