System Troubleshooting - Minor Fault
Recirculation or Underflow (UF) Valve Not Opening / Not Closing
(Mechanical)
Motor Separated From PVC
Continuing on from previous step.....
The motor did
turn 90 degrees. This
indicates that the motor and wiring
are fine. It points to a mechanical
issue with the PVC portion of the
ball valve itself. Place the Reclaim
in “Hand” to go into Fresh Water
Bypass. Loosen both unions and
Remove the PVC portion of the valve
assembly. Visually inspect the interior
of the valve. Is it dirty? Take a look at
the bottom of the valve and note the
“stem” of the valve.
Using a 1/2” wrench, rotate the valve
position. Clean the valve in the open
& closed positions.
Once the valve is clean, rotate it
several times - is it relatively easy to
do so? If not, continue on.
Locate the adjusting nut for valve
seat tension on one side of the valve.
Using a large adjustable wrench, turn
the adjusting nut counter-clockwise
about 1/8 of a turn.
Recheck the tension using the 1/2”
wrench on the stem. Feel better?
If so, re-assemble & test using the
touch screen toggle button. If all is
well, replace the valve assembly on
the machine and hand tighten the
unions.
Place the Reclaim back into “Auto”.
Valve Bottom View
SAFETY NOTE!!
NEVER PLACE
FINGERS INSIDE
OF ANY OF THE
PVC PORTION OF
A MOTORIZED
BALL VALVE
WITH THE MOTOR
ATTACHED!!!