Functional Overview
6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
ProSoft Technology, Inc.
Page 93 of 190
February 2, 2009
MSG Instruction Type
ControlLogix
Database Address
PLC2
PLC5 or SLC
PCCC CIP
Integer
0 0
N10:0
N10:0 Int_data[0]
999 999
N19:99
N19:99 Int_data[999]
1000 1000
N20:0
N20:0 Int_data[1000]
1999 1999
N29:99
N29:99
Int_data[1999]
2000 2000
N30:0
N30:0 Int_data[2000]
2999 2999
N39:99
N39:99
Int_data[2999]
3000 3000
N40:0
N40:0 Int_data[3000]
3999 4000
N49:99
N49:99
Int_data[3999]
MSG Instruction Type
ControlLogix
Database
Address
CIP Boolean
CIP Bit Array
CIP Byte
CIP Double Int
CIP Real
0 BoolData[0]
BitAData[0]
SIntData[0] DIntData[0] RealData[0]
999
BoolData[15984]
SIntData[1998]
1000 BoolData[16000]
BitAData[500]
SIntData[2000] DIntData[500] RealData[500]
1999
BoolData[31984]
SIntData[3998]
2000 BoolData[32000]
BitAData[1000] SIntData[4000] DIntData[1000] RealData[1000]
2999
BoolData[47984]
SIntData[5998]
3000 BoolData[48000]
BitAData[1500] SIntData[6000] DIntData[1500] RealData[1500]
3999
BoolData[63999]
SIntData[9998]
When using PLC5 or SLC commands, access to the database is through
simulated 'N' files. For example, to access database element 3012, use the file
address of N40:12. When using CIP Data Table Read or Write commands, use
the various data[ ] tag arrays described in the following table. For example, use
int_data[3012] to access database register 3012 as an integer value.
Data Type
Tag Name
Length of Each Element in
CIP message
Array Range for 4000
Element Database
BOOL
BOOLData[ ]
1
0 to 63999
Bit Array
BITAData[ ]
4
0 to 1999
SINT
SINTData[ ]
1
0 to 7999
INT
INT_Data[ ]
2
0 to 3999
DINT
DINTData[ ]
4
0 to 1999
REAL
REALData[ ]
4
0 to 1999
Before attempting to use the module on a network, verify that the DFNT module
is correctly configured and connected to the network. A network program such as
PING can be utilized to make certain the module can be seen on the network.
Use ProSoft Configuration Builder to verify correct operation, and to transfer
configuration files to and from the module.