6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Reference
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
Page 158 of 190
ProSoft Technology, Inc.
February 2, 2009
SLC5/05 Read Commands
Read commands transfer data to the SLC processor from the DFNT module. An
example rung used to execute a read command is shown in the following
diagram:
Set the
Read/Write
parameter to
Read
. The module supports a
Target Device
parameter value of
500CPU
or
PLC5
. In order to complete the configuration of
the MSG instruction, select the
Setup Screen
area of the MSG object. This
displays the following dialog box.
The
Target Device Data Table Address
must be set to a valid file element (that
is, N11:0) for SLC and SLC5 messages. The
MultiHop
option must be set to
Yes
. The
MultiHop
tab portion of the dialog box must be completed as displayed
in the following window:
The IP address corresponds to that set in the module's WATTCP.CFG file. The
slot number should be set to zero.
Summary of Contents for 6202-WA-DFNT-DFCM3