6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Reference
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
Page 124 of 190
ProSoft Technology, Inc.
February 2, 2009
Column Parameter
Description
Parameter
7
Slot Number
Processor slot number in Control/CompactLogix rack.
Use -1 for PLC5 & SLC processors.
8
Function Code = 150
Word Range Write Command.
9
File String
PLC-5 address as specified as an ASCII string. For
example, N10:300.
P1
10 to 12
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function writes one or more words of data to a PLC data table. This function
should work on the following devices: PLC-5.
Function Code #151 - Word Range Read (PLC-5 Command) (ASCII Address)
Column Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled and 1=Continuous.
2
Virtual Database Address
This parameter defines the database address of the first
data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.
6
Node Address
Address of unit to reach on the data highway.
7
Slot Number
Processor slot number in Control/CompactLogix rack.
Use -1 for PLC5 & SLC processors.
8
Function Code = 151
Word Range Read Command.
9
File String
PLC-5 address as specified as an ASCII string. For
example, N10:300.
P1
10 to 12
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function reads one or more words of data from a PLC data table. This
function should work on the following devices: PLC-5.
Function Code #152 - Read-Modify-Write (PLC-5 Command) (ASCII Address)
Column Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address for the
data to be associated with the command. The first
database register is used as the AND mask for the
command, and the second is used for the OR mask.
Values in the AND mask have the following definitions:
0=Reset and 1=Leave the Same. Values in the OR
mask have the following definitions: 0=Leave the Same
and 1=Set.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.