Configure the Module
6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
ProSoft Technology, Inc.
Page 39 of 190
February 2, 2009
Busy Timeout
0 to 65535
This parameter specifies the number of milliseconds to wait for the DF1 master
port to become available. If the DF1 master port is processing a command list
request, the busy flag will be set. The flag will remain busy until the
communication transaction is complete. If the port does not become available
before the busy timeout expires, the message will be aborted. If the master port
becomes available before this timeout expires, the request will be routed to the
master port.
ACK Timeout
0 to 65535
This parameter specifies the number of milliseconds to wait for a DLE-ACK
character sequence after a response is issued.
Sample Parameters
To enable pass-through mode, configure Port 1 on the module as a DF1 master
port using the DF1 full-duplex protocol. At least one command must be enabled
in the DF1 Port 0 Commands section. It is recommended to have one or more
seconds set for the Polling Rate.
The following illustrations show the use of the pass-through port functionality:
Wireless DF1 Pass-Through in Ad-Hoc mode
Wireless DF1 Pass-Through in Infrastructure mode