6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Reference
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
Page 150 of 190
ProSoft Technology, Inc.
February 2, 2009
Verify that the
CIP
radio-button is selected as the
Communication Method
. The
Path
specifies the message path from the ControlLogix processor to the module.
In the example above, the path is from the processor to the Enet module (1756-
ENET module in slot 2), the 2 represents the Ethernet port on the 1756-ENET
module and the last portion of the path is the IP address of the DFNT module to
reach (192.168.0.75).
More complex paths are possible if routing to other networks using multiple 1756-
ENET modules and racks. Refer to the Knowledge Document 10803, Control
Logix Gateway: Ethernet Communications for a full discussion of Ethernet routing
and path definition.
CIP Data Table Operations
This method of data transfer uses CIP messages to transfer data between the
ControlLogix processor and the module. Tag names define the elements to be
transferred. The following topics describe the support for the read and write
operations.
CIP Data Table Write
CIP data table write messages transfer data from the ControlLogix processor to
the DFNT module. An example rung used to execute a write command is shown
in the following diagram: