6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Configure the Module
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
Page 44 of 190
ProSoft Technology, Inc.
February 2, 2009
ENQ Delay
0 to 65535
This parameter specifies the number of milliseconds to wait after a DLE-ACK is
received from a slave using half-duplex mode before the DLE-ENQ request is
made for data.
Minimum Command Delay
This parameter specifies the number of milliseconds to wait between issuing
each command. This delay value is not applied to retries.
Error Delay Counter
0 to 65535
This parameter specifies the number of polls to be skipped on the slave before
trying to re-establish communications. After the slave fails to respond, the master
will skip commands to be sent to the slave the number of times entered in this
parameter.
Command Control Reg
0 to 3900
This parameter controls the execution of commands in the user list by setting a
value of 0, 1, or 2. If a user defines the list with a type code of zero for all
commands, no commands will execute. If the value in the first control register is
changed to one, command zero will execute continuously. The feature can be
disabled by setting the parameter value to -1 or by omitting the item name from
the configuration file. This feature requires 100 registers of the module's
database.
First File
0 to 100
This parameter is used when a request for a file is received on the
communication port. This field is required when responding to PLC5 and SLC
DF1 commands. Use this parameter to define the virtual file(s) to be simulated on
the module.
File Size
Range 1 to 1000
This parameter specifies the size of each file to be simulated on the module. All
files simulated are defined to have the same assigned size.
File Offset
This parameter sets the database register location of the first element in the first
file simulated in the module. All offsets in the first file and subsequent files will be
computed using the address specified. Enter a value in the range of 0 to 4999.