- 49 -
5.2.8. Select Group
It is a menu to set currently applied Primary Group among 4 setting groups.
Default value is set 1. If Sel Auto Group is selected as “YES”, it selects automatically the
primary group and reverse group, depending on the power flow. If the current flows from
load side to source side, side flows from Load side to power side, the reverse group is
applied.
[ S e t t i n g
M E N U ]
1 . F u n c G r o u p 1
2 . F u n c G r o u p 2
3 . F u n c G r o u p 3
4 . F u n c
G r o u p 4
> 5 . S e l e c t
G r o u p
[ S e l
G r o u p
M e n u ]
> 1 . P r i m a r y
G r o u p
2 . S e l
A u t o
G r o u p
3 . R e v e r s e
G r o u p
[ P r i m a r y
G r o u p ]
S E T
:
1
( 1
-
4
:
1 )
<Figure 5-14> Setting Menu
Under
Voltage
U-V Pickup
30~98
75
1
%
Set pickup level for under voltage
U-V Op Time
0.1~100
3
0.1
sec
Set operation time for under voltage
Use Func
OFF/ALM/TRIP
OFF
Set whether under voltage function is
available
Over
Voltage
O-V Pickup
102~150
120
1
%
Set pickup level for over voltage
O-V Op Time
0.1~100
3
0.1
sec
Set operation time for over voltage
Use Func
OFF/ALM/TRIP
OFF
Set whether over voltage function is
available
Under
Frequency
U-F Pickup
47~59.98
49.8
0.01
Hz
Set pickup level for under frequency
U-F Op Time
0.1~60
1
0.1
sec
Set operation time for under
frequency
Use Func
OFF/ALM/TRIP
OFF
Set whether under frequency function
is available
Over
Frequency
O-F Pickup
50.02~63.00
60.02
0.01
Hz
Set pickup level for over frequency
O-F Op Time
0.1~60
1
0.1
sec
Set operation time for over frequency
Use Func
OFF/ALM/TRIP
OFF
Set whether over frequency function is
available
Close
Interlock
Live Load
NO/YES
NO
Select whether live load is available
Sync Fail
NO/YES
NO
Select whether sync fail is available
Loop
Automation
Loop Selection
OFF/FEEDER/MI
D/TIE
OFF
Select operating mode for the recloser
Deadbus Open
Time
0~600
0
1
sec
Set open time for determining
distribution line’s dead line state
Tie Sw Open
Time
0~600
0
1
sec
Set open time for tie sw
Tie Sw Source
BOTH/ABC/RST
BOTH
Select whether Tie sw source is ABC or RST
Tie Sw Close
Time
0~600
0
1
sec
Set close time for tie sw
Rec Block Time
0~600
60
1
sec
Set Reclosing Blocking Time
Enable Restore
Disable/Enable
Disable
Set whether restoration after clearing
fault
Rec Close Time
0~600
30
1
sec
Set recloser closing time after open
Tie On Delta I
5~95
5
1
%
Set delta I level to restore for Tie
recloser after fault
Summary of Contents for RECLOSER
Page 1: ...User Manual Document Version 1 5 Feb 28 2019 http powersys kr http www powersys kr...
Page 14: ...8 3 5 Mechanical Performance and Size Weight 3 5 kg FRONT VIEW Figure 3 1 Front View...
Page 15: ...9 SIDE VIEW 343 00 310 00 91 00 Figure 3 2 Side View...
Page 16: ...10 TOP VIEW 84 0 260 0 225 0 1 0 0t Figure 3 3 Top View...
Page 17: ...11 REAR VIEW 180 0 120 0 Figure 3 4 Rear View...
Page 22: ...16 Controller PCB 215 00 103 90 121 10 112 50 112 50 235 00 205 00 Figure 3 8 Controller PCB...
Page 69: ...63...
Page 71: ...65 Example configuration file...
Page 73: ...67 2 TC Curve 1 4 100 101 10 1 100 101 102 Time sec Current In Multiplies of Setting 1 2 3 4...
Page 74: ...68 3 TC Curve 5 8 100 101 10 1 100 101 102 Time sec Current In Multiplies of Setting 5 6 7 8...
Page 77: ...71 6 TC Curve A D 100 101 10 1 100 101 102 Time sec Current In Multiplies of Setting A B C D...
Page 78: ...72 7 TC Curve E M 100 101 10 1 100 101 102 Time sec Current In Multiplies of Setting E K L M...
Page 79: ...73 8 TC Curve N T 100 101 10 1 100 101 102 Time sec Current In Multiplies of Setting N P R T...
Page 80: ...74 9 TC Curve V Z 100 101 10 1 100 101 102 Time sec Current In Multiplies of Setting V W Y Z...