Min run time collector pump
(3831)
The collector pump is periodically switched on for the running time set here.
Collector start function ON
(3832)
Collector start function OFF
(3833)
The time that the collector start function starts or stops is set here.
Collector start funct grad
(3834)
As soon as there is a temperature increase on the collector sensor, the collector
pump switches on. The higher the value here is set, the larger the temperature
increase must be.
Collector frost protection
(3840)
In order to prevent freezing of the collector, the collector pump will be activated
in case of frost danger.
Collector overtemp prot
(3850)
In case of overheating danger, charging of the storage will be continued to re-
move heat. When reaching the storage safety temperature charging of the stor-
age will be interrupted.
Evaporation heat carrier
(3860)
Pump protecting function, to prevent overheating of the collector pump in case of
evaporating danger of the heat carrying medium due to high collector tempera-
ture.
Antifreeze
(3880)
Information of the antifreeze used.
Antifreeze concentration
(3881)
Input of antifreeze concentration for usage measurement of solar energy.
Pump capacity
(3884)
Input of the flow of the installed pump for calculation of the brought in volume
for usage measurement.
Pulse valency
(3887)
Defines the flow per pulse for the Hx inlet. The Hx inlet must be configured to
pulse count for this.
8.18 Solid fuel boiler
Locks other heat sources
(4102)
If the solid fuel boilers are activated, other heat generators, e.g. oil./gas boilers,
are blocked, as soon as an increase in the boiler temperature is discovered that
points to the exceeding of the comparative temperature (prog. no. 4133).
Setpoint min
(4110)
The boiler pump is only put into operation if the boiler temperature has reached
the minimum setpoint set here in addition to the necessary temperature differ-
ence.
Programming
92
Paramount three 30-115 kW
396532 05.11
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...