7. Loosen the gas connection pipe at the gas valve (
4
) and remove gas valve (
5
)
8. Loosen the 5 fastening screws at the mixing channel/heat exchanger
9. Remove (
6
) bracket
10. Remove intake muffler
11. Pull out the burner together with mixing channel and fan to the front (
7
)
12. Clean burner pipe with soft brush
Caution: Use new seals!
When re-fitting, new gaskets should be used, particularly for the the gas connect-
ing pipe.
10.5 Protection against contact
Danger of electric shock!
To ensure shock-proof protection, all parts of the device
to be screwed on, have to be screwed on correctly; especially the cover parts!
Maintenance
396532 05.11
Paramount three 30-115 kW
121