Function
Prog.
no.
Level
1)
Standard value
Priority/state source 9
Parameters see Priority/state source 1 (prog.-no. 8100)!
8116
C
Priority/state source 10
Parameters see Priority/state source 1 (prog.-no. 8100)!
8118
C
Priority/state source 11
Parameters see Priority/state source 1 (prog.-no. 8100)!
8120
C
Priority/state source 12
Parameters see Priority/state source 1 (prog.-no. 8100)!
8122
C
Priority/state source 13
Parameters see Priority/state source 1 (prog.-no. 8100)!
8124
C
Priority/state source 14
Parameters see Priority/state source 1 (prog.-no. 8100)!
8126
C
Priority/state source 15
Parameters see Priority/state source 1 (prog.-no. 8100)!
8128
C
Priority/state source 16
Parameters see Priority/state source 1 (prog.-no. 8100)!
8130
C
Cascade flow temp
8138
C
Cascade flow temp setp
8139
C
Cascade return temp
8140
C
Cascade return temp setp
8141
C
Source seq ch'over current
8150
C
Diagnosis generator
Boiler pump Q1
8304
E
Boiler pump speed
8308
E
Boiler temperature
8310
C
Boiler setpoint
8311
C
Boiler switching point
8312
C
Boiler return temp
8314
C
Fan speed
8323
C
Set point fan
8324
C
PWM speed control (Proz)
8325
C
Burner modulation
8326
C
Ionization current-actual value
8329
C
Hours run 1st stage
8330
Eu
Start counter 1st stage
8331
C
Hours run heating mode
8338
Eu
Hours run DHW
8339
Eu
Phase number
8390
E
State Collector pump 1 (Q5)
8499
C
Solar ctrl elem buffer
8501
E
Programming
396532 05.11
Paramount three 30-115 kW
65
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...