Function
Prog.
no.
Level
1)
Standard value
Switching diff on HCs
2454
E
4°C
Switching diff off min HCs
2455
E
5°C
Switching diff off max HCs
2456
E
7°C
Switching diff on DHW
2460
E
5°C
Switching diff off min DHW
2461
E
6°C
Switching diff off max DHW
2462
E
8°C
Pressure switch shutdown
Start prevention | Lockout position
2500
E
Start prevention
*) kW-settings are approximate values. Exact values can for example are determined by the gas meter.
Cascade
Lead strategy
Late on, early off | Late on, late off | Early on, late off
3510
E
Late on, late off
Release integral source seq
3530
E
50°C*min
Reset integral source seq
3531
E
20°C*min
Restart lock
3532
E
300 s
Switch on delay
3533
E
10 min
Auto source seq ch'over
3540
E
100 h
Auto source seq exclusion
None | First | Last | First and last
3541
E
None
Leading source
Source 1 | Source 2 | Source 3 | Source 4 | Source 5 | Source 6 | Source 7
| Source 8 | Source 9 | Source 10 | Source 11 | Source 12 | Source 13 |
Source 14 | Source 15 | Source 16
3544
E
Source 1
Return setpoint min
3560
E
8°C
Temp differential min
3590
E
- - -°C
Solar
Temp diff on
3810
C
8°C
Temp diff off
3811
C
4°C
Charg temp min DHW st tank
3812
I
- - - °C
Temp diff on buffer
3813
E
- - - °C
Temp diff off buffer
3814
E
- - - °C
Charging temp min buffer
3815
E
- - - °C
Temp diff on swi pool
3816
E
- - - °C
Temp diff off swi pool
3817
E
- - - °C
Charging temp min swi pool
3818
E
- - - °C
Charging prio storage tank
None | DHW storage tank | Buffer storage tank
3822
E
DHW storage tank
Charging time relative prio
3825
E
- - - min
Waiting time relative prio
3826
E
5 min
Waiting time parallel op
3827
E
- - - min
Delay secondary pump
3828
E
60 s
Collector start function
3830
E
- - -
Min run time collector pump
3831
E
20 s
Collector start function On
3832
E
07:00 (h:min)
Programming
396532 05.11
Paramount three 30-115 kW
55
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...