Note:
At the same time, the exhaust gas collecting tray should be checked for soil-
ing and if needed should be cleaned (rinsed).
10.4 Removing gas burner
Remove the gas burner before cleaning the heating surfaces.
Fig. 29: Removing gas burner
Paramount three 30/40
Paramount three 60
2
3
1
3
2
5
4
6
7
Paramount three 70
Paramount three 95/115
1
3
2
5
4
6
7
1
3
2
5
4
6
7
Removing gas burner
(
Fig. 29
)
1. Disconnect the electrical connection cables to the fan at the coupler
2. Pull off air hose from the fan
3. Pull the connector from the electrodes
4. Undo fixing screw (
1
) in the inlet silencer at the top of the Paramount
5. Loosen the screw connections of the gas connection pipe at the mixing channel
and the gas valve
6. Remove the gas connection pipe (
2
) and the gas jet (
3
)
Maintenance
120
Paramount three 30-115 kW
396532 05.11