Function
Prog.
no.
Level
1)
Standard value
Flow setp compensation Tv
5145
E
30 s
Full charging with B36
No |Yes
5146
E
No
Min start temp diff Q33
5148
E
-3°C
Excess interm circ temp del
5151
E
30 s
Configuration
Heating circuit 1
Off | On
5710
C
ON
Heating circuit 2
Off | On
5715
C
Off
Heating circuit 3
Off | On
5721
C
Off
DHW sensor
DHW sensor B3 | Thermostat
5730
E
DHW sensor B3
DHW controlling element Q3
No charging request | Charging pump | Diverting valve
5731
F
Charging pump
Basic pos DHW div
Last request | Heating circuit | DHW
5734
E
Heating circuit
DHW separate circuit
Off | On
5736
E
Off
Contact type DHW div valve
Position on DHW | Position on HC
5737
E
Position on DHW
Ctrl boiler pump/DHW valve
All requests | Request HC1/DHW only
5774
E
All requests
Solar controlling element
Charging pump | Diverting valve
5840
E
Charging pump
External solar exchanger
Commonly | DHW storage tank | Buffer storage tank
5841
E
Commonly
Combi storage tank
No |Yes
5870
E
No
Relay output QX1
None | Circulating pump Q4 | El imm heater DHW K6 | Collector pump
Q5 | Cons circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 |
Heat circuit pump HC3 Q20 | Cons circuit pump VK2 Q18 | System
pump Q14 | Heat gen shutoff valve Y4 | Solid fuel boiler pump Q10 |
Time program 5 K13 | Buffer return valve Y15 | Solar pump ext exch
K9 | Solar ctrl elem buffer K8 | Solar ctrl elem swi pool K18 | Swim-
ming pool pump Q19 | Cascade pump Q25 | St tank transfer pump
Q11 | DHW mixing pump Q35 | DHW interm circ pump Q33 | Heat re-
quest K27 | Heat circuit pump HC1 Q2 | Heat circuit pump HC2 Q6 |
DHW ctrl elem Q3 | Status output K35 | Status information K36 | Flue
gas damper K37 | Fan shutdown K38
5890
C
Alarm output K10
Relay output QX2
Parameters see Relay output QX1 (prog.-no. 5890)!
5891
C
Heat circuit pump HC1
Q2
Relay output QX3
Parameters see Relay output QX1 (prog.-no. 5890)!
5892
C
DHW controlling element
Q3
Programming
58
Paramount three 30-115 kW
396532 05.11
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...