Pulse count
: By querying the input the low frequency pulse, e.g. for flow meas-
urement is recorded.
-
Checkb sign flue gas damper
: Checkback via input H1 in case of activated flue gas
damper control.
-
Start prevention
: With this input a burner start can be prevented.
-
Consumer request VKx 10V
: The application nodes external load x receives a volt-
age signal (DC 0-10 V) as heat request. The linear curve is defined via two fix
points (voltage value 1/function value 1 and voltage value 2/function value 2
(only applies to H1).
-
Preselected output:
The source receives a voltage signal (DC 0 - 10 V) as output
request. The linear curve is defined via two fix points (voltage value 1/function
value 1 and voltage value 2 / function value 2 (only applies to H1).
-
Flow measurement
: Here a flow sensor can be connected which indicates the
flow volume via a frequency (only applies to H4).
Contact type H1/H4/H5/H2
(5951, 5971, 5978)
With this function, the contacts can be set as resting contact (contact closed,
must be opened for activating the function) or as working contact (contact
opened, must be closed for activating the function).
Voltage value 1/2 H1
(5953, 5955)
Function value 1/2 H1
(5954, 5956)
The linear sensor curve is defined over two fixed points. The setting is made with
two parameter pairs for
Function value
and
Voltage value
(F1 / U1 and F2 / U2).
The function value is specified to a factor of 10, i.e. if you require 100 °C, you
should select "1000".
Frequency values 1/2 H4
Function values 1/2 H4
(5973-5976)
The linear sensor curve is defined over two fixed points. The setting is done with
two parameter pairs for
function value
and
frequency value
(F1 / U1 and F2 / U2).
Fig. 26: Example for two different sensor curves
y
flow
Function extension module
1/2
(6020/6021)
Determination of the functions, which will be controlled via the extension mod-
ules 1 and 2.
-
Multifunctional
: Possible functions for multi-functional relay outputs and inputs
see prog.-no. 6030 to 6035.
-
Heating circuit 1
For this usage, the respective settings can be adjusted in the
menu point Heating circuit 1.
-
Heating circuit 2
For this usage, the respective settings can be adjusted in the
menu point Heating circuit 2.
Programming
396532 05.11
Paramount three 30-115 kW
103
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...