5.12 CO2 -Content
The CO
2
content in the exhaust gas must be checked during commissioning and
during regular maintenance of the boiler, as well as, after reconstruction work on
the boiler or on the exhaust gas system.
CO
2
-content during operation see section
Technical data
.
Caution! Risk of damage of the burner!
Too
high
CO
2
-values can lead to incomplete combustion (high CO-values) and
damage to the burner.
Too
low
CO
2
-values can lead to ignition problems.
The CO
2
-value has to be set by modifying the gas pressure at the gas valve (see
Fig. 8
).
The air quantity set in the factory must not be changed.
5.13 Changing over from LPG to
natural gas and vice versa
Danger! Danger of life by gas!
The gas type of the Paramount must only be modified by an GasSafe heating engi-
neer. Use the Potterton conversion set for LPG (accessory).
- Paramount disconnect from the mains.
- Close gas shut-off facility.
- Replace gas jet and burner.
- Amend operation parameters as necessary
- Use enclosed new seals!
The CO
2
-content has to be set by adjusting the nozzle pressure at the gas valve
(See section :
Guide line for nozzle pressure)
The CO
2
-content must be between the values according to section
Technical Data
at full load as well as low load.
Installation
28
Paramount three 30-115 kW
396532 05.11
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...