Function
Prog.
no.
Level
1)
Standard value
Swimming pool circuit
Flow temp setp cons request
1959
C
70°C
DHW charging priority
No |Yes
1974
E
Yes
Excess heat draw
Off | On
1975
E
ON
With buffer
No |Yes
1978
E
Yes
With prim contr/system pump
No |Yes
1980
E
Yes
Swimming pool
Setpoint solar heating
2055
Eu
26°C
Setpoint source heating
2056
Eu
22°C
Charging priority solar
No |Yes
2065
E
No
Swimming pool temp max
2070
E
32°C
With solar integration
No |Yes
2080
E
Yes
Primary contr/system pump
Flow temp setpoint min
2110
E
8°C
Flow temp setpoint max
2111
E
80°C
Syst pump on heat gen lock
Off | On
2121
E
Off
Mixing valve boost
2130
E
0°C
Actuator running time
2134
E
120 s
Boiler
Setpoint min
2210
F
20°C
Setpoint max
2212
F
30/40: 85°C
60-115: 88°C
Setpoint manual control
2214
Eu
60°C
Burner running time min
2241
E
1 min.
Burner off time min
2243
E
3 min.
SD burner off time
2245
E
20°C
Pump overrun time
2250
E
2 min.
Pump overr time after DHW
2253
E
1 min.
Frost prot plant boiler pump
Off | On
2300
E
Off
Boiler pump on heat gen lock
Off | On
2301
E
Off
Impact heat generation lock
Heating mode only | Heating and DHW mode
2305
E
Heating mode only
Temp differential max
2316
C
45°C
Temp differential nominal
2317
C
15°C
Programming
396532 05.11
Paramount three 30-115 kW
53
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...