Heating circuit 3
For this usage, the respective settings can be adjusted in the
menu point Heating circuit 3.
-
Solar DHW
: For this usage, the respective settings can be adjusted in the menu
point Solar.
-
Primary contr/system pump
: For this usage, the respective settings can be adjus-
ted in the menu point Primary contr/system pump.
Sensor input BX21/BX22
(6040 - 6043)
Sensor inputs for the modules 1 and 2.
Functions in addition to the basic functions will be possible by configuring the
sensor inputs BX21 and BX22.
Explanations see prog.-no. 5930).
Function input H2 EM1/2
(6046, 6054)
Explanations see prog.-no. 5950.
Contact type H2 EM 1/2
(6047, 6055)
Explanations see prog.-no. 5951.
Voltage values 1/2 H2 mod-
ule 1-2
(6049, 6051, 6057, 6059)
Function values 1/2 H2 mod-
ule 1-2
(6050, 6052, 6058, 6060)
The linear sensor curve is defined over two fixed points. The setting is made with
two parameter pairs for
Function value
and
Voltage value
(F1 / U1 and F2 / U2).
Fig. 27: Example for heat demand 10 V and cooling demand 10 V
Flow setpoint
[°C]
F2=130
F2=100
F1=0
Voltage at Hx
[V]
U1=0
0,15
U1=10
F1
Function value 1
F2
Function value 2
U1
Voltage value 1
U2
Voltage value 2
Programming
104
Paramount three 30-115 kW
396532 05.11
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...