8.3 Setting table
- Not all parameters displayed in the display are listed in the setting table.
- Depending on the plant configuration, not all parameters listed in the setting ta-
ble are displayed in the display.
- In order to get to the setting levels: Enduser (Eu), Commissioning (C) and Engi-
neer (E), press OK button; after this, press and hold the information (i) button for
3 seconds, select the required level with the rotating knob and acknowledge
with the OK button.
Tab. 7: Setting the parameters
Function
Prog.
no.
Level
1)
Standard value
Time and date
Hours/minutes
1
Eu
00:00 (h:min)
Day/month
2
Eu
01.01 (day. month)
Year
3
Eu
2004 (year)
Start of summertime
5
E
25.03 (day.month)
End of summertime
6
E
25.10 (day, month)
Programming unit
This parameter is only visible in the room device!
Language
20
Eu
English
Info
Temporarily | Permanently
22
E
Temporarily
Contrast of display
25
E
Operation lock
Off | On
26
E
Off
Programming lock
Off | On
27
E
Off
Units
°C, bar | °F, PSI
29
Eu
°C, bar
Save basic settings
No | Yes
This parameter is only visible in the room device!
30
E
No
Activate basic settings
No | Yes
This parameter is only visible if a suitable standard setting is
available in the programming unit.
31
E
No
Use as
Room unit 1 | Room unit 2 | Room unit 3/P | Operator unit 1 | Opera-
tor unit 2 | Operator unit 3 | Service unit
This parameter is only visible in the room device!
40
C
Room controller 1
Room controller 1 assignment
Heating circuit 1 | Heating circuits 1 and 2 | Heating circuits 1 and 3/P
| All heating circuits
This parameter is only visible in the room device, as the operating
unit in the boiler is fixed programmed for the operating device!
42
C
Heating circuit 1
Programming
396532 05.11
Paramount three 30-115 kW
45
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...