3.2 Specification
Tab. 2: Specification
Model
Paramount three
30
40
60
80
95
115
Product-ID-No.
CE-0085BL0514
VDE-Reg.-No.
VDE-mark
International protection
IPx4D
Gas category
II
2H3+
Devices category
B
23
, B
33
, C
13X
, C
33X
, C
43X
, C
53
, C
63X
, C
83
Nominal heat input
range
Natural
Gas
Heating
mode
kW 5,6-30,0
9,0-38,0 14,0-58,0 21,0-77,0 20,0-95,0 25,0-115,0
Nominal heat out-
put range
Natural
Gas
80/60°C
kW 5,4-29,2
8,7-36,8 13,4-56,3 20,3-74,7 19,4-92,2 24,3-111,7
50/30°C
kW 6,0-31,3
9,6-39,0 14,9-60,1 22,6-79,7 21,4-98,1 26,7-118,6
Standard efficiency
75/60°C
106,0
106,0
106,0
106,0
106,0
106,0
40/30°C
109,0
109,0
109,0
109,0
109,0
109,0
pH-value condensate
-
4-5
4-5
4-5
4-5
4-5
4-5
Volume condensate
40/30°C
l/h 0,83-3,00 1,19-2,84 1,78-4,71 2,53-6,46 2,75-8,42 3,85-9,61
NO
X
-Standard emission fac-
tor
mg/
kWh
17
20
20
20
25
25
CO-Standard emission factor
mg/
kWh
5
10
10
10
20
20
Data for design of the chimney to DIN EN 13384 (room air-depending operation)
Exhaust gas tem-
perature (full load)
Full
load
80/60°C
°C
66
75
71
73
73
77
Low
load
°C
53
56
59
59
59
60
Full
load
50/30°C
°C
46
53
54
54
51
56
Low
load
°C
33
35
34
35
32
33
Exhaust gas mass
flow
Natural
Gas
80/60°C
g/s 2,8-14,8
4,4-18,7
6,9-28,5 10,3-37,9 9,8-46,7
12,3-56,6
50/30°C
g/s 2,5-14,1
4,1-18,0
6,4-27,4
9,7-36,4
9,1-44,8
11,3-54,4
Exhaust gas mass
flow
Pro-
pane
80/60°C
g/s 2,6-14,1
4,2-17,8
6,6-27,2
9,8-36,1 14,1-44,6 16,4-53,9
50/30°C
g/s 2,4-13,4
3,9-17,1
6,1-26,1
9,2-34,6 13,3-42,6 15,4-51,7
CO2-content
natural gas
Natural
Gas
%
8,3 - 8,8
CO2-content LPG
Pro-
pane
%
10,3 - 10,7
Draft requirement
mbar
0
Max. delivery pressure at exhaust gas out-
let
mbar
1,1
1,1
1,1
1,1
1,5
1.8
Exhaust gas/air supply connection
mm
80/125
110/160
Exhaust gas value group to DVGW G636
-
G6
Technical Data Paramount Three 30-115
12
Paramount three 30-115 kW
396532 05.11
Summary of Contents for Gas condensing boiler
Page 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Page 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Page 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Page 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Page 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Page 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...