PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 19
3.7.1 Service Mode
When the service mode is active (ON) the alarms are not transmitted to the alarm relays (in case of calibration or
service work). The service mode is reset automatically after 60 minutes or manually in the menu “Service Mode”.
Symbol
Description
Default
Status
Function
Off
Service Mode
Off
Off = Alarms activate the associated alarm relays
On = Alarms are not transmitted to the alarm relays
3.7.2 Software Version
Symbol
Description
Default
Status
Function
GC03-
XX
Software
Version
XX = Software Version
3.7.3 Maintenance Concept
Integrated in the SPC-03 system there is a control of the maintenance intervals required by law or by the
customer. At commissioning or after maintenance the number of days until the next due maintenance is entered =
Reset of the maintenance message (service phone no.). When the days counter reaches zero, the failure signal is
activated the following morning at 9 o’clock, and the phone no. of the service technician occurs in the display. The
remaining days until the next maintenance can be read from the menu “Maintenance in”.
The service phone no. can be entered individually in the next menu.
Symbol
Description
Defa
ult
Function
XXX
Maintenance in
Remaining days until the next maintenance
XXX
Maintenance interval
912 Reset of the maintenance message by entering the number of
days until the next maintenance
0853....
Phone No.
Input of the individual service phone no.
3.7.4 Average Function
For each active sensor point the Single Point Gas Controller calculates the arithmetic average value out of 10
measurements got within the time unit defined in the menu “AV Time“. This average value is indicated in the menu
“Sensor Reading” next to the current value. At each sensor point the control mode (current or average value) is
defined for the alarm evaluation.
The alarm evaluation of the control mode average value is overlaid by the current value, when the current value
exceeds the alarm Stage/Set Point defined in the menu “AV Overlay“. The overlay is delayed by the time factor
defined in this menu. Whit time factor 0 sec. the overlay is not active.
Symbol
Description
Default
Status
Function
120 s
120 ppm
AV Overlay 120 s
120 ppm
sec. = Delay time of average value overlay. 0 = No overlay function
ppm = Alarm Stage/Set Point of average overlay
1800 s
AV Time
1800 s
sec. = Time for the calculation of the average value
Analog Output
Analog Output 1
Max.
Calibration AO 1
4.0=4mA 20=20mA
See 3.7.7
See 3.7.7