PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 09
R 01
OFF
3.3
Relay Status
The SPC3 has two alarm relays (R01 / R02) and two open collector outputs (R03 / R04). In the following description
they are referred to as alarm relays.
Display of the actual status of alarm relays. Manual operation of the alarm relays.
Symbol Description Setting
Status Function
R 01
Relay No. 01
Select Relay No.
OFF
Relay Status
OFF
OFF
ON
Manual OFF
Manual ON
= Relay OFF (No gas alarm)
= Relay ON (Gas alarm)
= Relay manual OFF
= Relay manual ON
3.3.1
Manual Operation of the Relays
The manual operation of the alarm relays is managed in the menu “Relay Status”. If a relay is in the manual ON or
OFF status, the orange/ red alarm LED at the Gas Controller is lit continuously.
The external operation of the alarm relay via an assigned digital input has priority to the manual operation in the menu
"Relay Status" and to gas alarm.
Relays manually operated in the menu “Relay Status” are deleted again by selecting the function "Automatic."
Acknowledging the relays in latching mode is also effected in this menu.
Select
the
relay
Select
the
function
of
manual
operation
Manual
ON =
Relay
ON
Select
the
function
Manual
OFF
=
Relay
OFF
Automatic
=
Delete
manual
operation.
Reset? =
Reset
of
a
latching
mode.
Take over the
f
unction
R 01
OFF
Manual ON
Manual OFF
Manual OFF