PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 15
3.6.1
Activate – Deactivate SP
Symbol Description
Setting
Status Function
SP 01*
Measuring point
Selection SP No.
Active
SP Status
Not
active
Active = Sensor point activated at the controller
Not active = Sensor point not activated at the controller
*SP01 = On Board sensor
*SP02 = External Transmitter (optional)
3.6.2
Selection Gas Type
Assign gas type to attached gas transmitters.
Symbol Description
Setting
Status Gas type
Unit
Measuring
range
1
SP 01
Measuring point
CO
Ex
NO
NO
2
NH
3
O
2
CO
2
SO
2
H
2
S
CL
2
ETC
VOC
R401
R402
R408
R409
R404
R416
R502
R410
R411
R11
R123
R134
R22
TEM
RH
CO
2
TOX
Carbon monoxide
Combustible gas
Nitrogen oxide
Nitrogen dioxide
Ammonia
Oxygen
2
Carbon dioxide
Sulphur dioxide
Hydrogen sulphide
Chlorine
Ethylene oxide
Air quality
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Temperature
Humidity
Carbon dioxide
Toxic gas
ppm
%LEL
ppm
ppm
ppm
%V/V
ppm
ppm
ppm
ppm
ppm
%
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
°C
% RH
ppm
ppm
0 – 250
0 – 100
0 – 50
0 – 25
0 – 300
0 – 25
0 – 2000
0 – 100
0 – 200
0 – 100
0 – 20
0 – 100
0 – 2000
0 – 2000
0 – 2000
0 – 2000
0 – 300
0 – 300
0 – 300
0 – 300
0 – 300
0 – 300
0 – 300
0 – 300
0 – 300
0 – 50
0 – 100
0 – 5000
0 - XX
1
Recommendation without obligation
2
Decreasing signal at oxygen measurement!