PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 08
SP 01
A1 A2
3.1.3
System Errors
The following system error messages are recorded:
SP 02 > 22 mA
Current signal at analog input > 22 mA / 11 VDC. (External Transmitter)
Cause:
Short-circuit at analog input or transmitter not calibrated, transmitter defective.
Solution:
Check cable to transmitter, make calibration, and replace the transmitter.
SP 02 < 3 mA
Current signal to analog input < 3 mA / 1,3 VDC. (External Transmitter)
Cause:
Wire breaking at analog input or transmitter not calibrated, transmitter defective.
Solution:
Check cable to transmitter, make calibration, replace the transmitter.
GC Error:
Internal communication error I/O Board to LCD Board.
Cause: Internal
error.
Solution:
Change
the
Gas
Controller
module.
Maintenance:
System maintenance is necessary.
Cause: Maintenance
date
exceeded.
Solution:
Make
the
maintenance.
3.2
Stage Status
Display of the actual alarms in plain text in the order of their arrival. Only those measuring points are displayed, where
at least one alarm is active. Changes are not possible in this menu.
Symbol Description Function
SP 01
Measuring
(SP) Point No.
AX
Stage Status
A1 = Alarm 1 ON
A2 = Alarm 2 ON
A3 = Alarm 3 ON
A4 = Alarm 4 ON