PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 10
SP 01 CO ppm
50 *AV 33 CV
3.4
Menu Sensor Reading
In this menu the current value (CV) with gas unit and gas type for each active sensor point (SP) is displayed. At control
mode average value (AV) is the average value additional displayed.
Symbol Description
Setting
Status
Function
SP 01
Measuring P. No.
Selection of SP No
CO
Gas type
CO
See 3.6.2
ppm
Gas unit
See 3.6.2
CV
Current value
CV
Current value of gas concentration
AV
Average value
Average value (10 measured values within the time unit)
*
Control mode
Display of selected control mode (CV or AV)
Not active Status SP
Not active SP not active
Error
Fault SP
Current signal < 3 mA or > 22 mA
3.5
Menu Relay Setups
Display and change of the setups for each alarm relay
(Main
menu)
(Select
relay
No.)
Relay
mode
See
3.5.1
Relay
function
See
3.5.2
Activate
latching
mode
See
3.5.3
Definition
of
horn
function
See
3.5.4
Definition
of
external
relay
operation
See
3.5.5
Set
delay
time
ON
See
3.5.6
Set delay time OFF
See
3.5.6
Relay Mode
De- energized
Static / Flash
0 s
Relay Setup
R 01
Latching Mode
No
Time Quiet. DI
0s 0 0
External Mode
DI: ON = 0: OFF = 0
Delay ON Time
0 s
Delay OFF Time
0 s