3.5.1
Relay Mode
Definition of relay mode:
Symbol Description Setting
Status
Function
R 01
Relay No.
Selection of relay
De-
energized Relay Mode
energized De-energized
Energized
= Alarm ON = Relay ON
= Alarm ON = Relay OFF
3.5.2
Relay Function Static / Flash
Definition of relay function
Symbol Description Setting
Status
Function
R 01
Relay No.
Selection of relay
0 Function 0
0 = Relay function static
> 0 = Relay function flashing (= Time period in sec.)
Impulse / Break = 1:1
3.5.3
Latching Mode
Definition of latching function
Symbol Description Setting
Status
Function
R 01
Relay No.
Selection of relay
No
Latching Mode No
No
Yes
= Latching mode non active
= Latching mode active
Acknowledging a latching relay in the menu “Relay Status“ is only possible if the gas concentration is again lower than
the alarm Stage/Set Point including hysteresis. In this case the status latching occurs in the display.
Example: Alarm relay R2 with latching mode
Alarm 2
Display in the Menu
Status Relay
Relay 2
Reset in the Menu
Status Relay
On
Off
On
Off
On
Off
R2
Off
R2
On
R2
On
R2
On
R2
Latching
R2
Off
Gas concentration higher lower than threshold