PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 13
3.5.5
External Relay Operation
Assignment to a digital input (DI) for external switching of the alarm relay (ON and/or OFF). This function has priority
to gas alarm and/or manual switching in the menu “Relay Status“.
Symbol Description Setting
Status Function
R 01
Relay No.
Relay Selection
DI-ON
External On
0
If digital input closed, relay switches ON
DI-OFF
External Off
0
If digital input closed, relay switches OFF
3.5.6
Delay Mode of the Relay.
Delay time ON starts when the alarm is released and/or delay time OFF starts when the alarm returns to normal
condition.
Symbol Description
Setting
Status Function
R 01
Relay No.
Relay Selection
0 s
Delay Time ON 0
Mode ON: Relay is only activated at the end of the defined time
(sec.) 0 sec. = No delay
0 s
Delay Time OFF 0
Mode OFF: Relay is only deactivated at the end of the defined
time (sec.) 0 sec. = No delay
3.6
Menu SP Setups
Display and change of setups, assignment of alarms to alarm relays and activation of Sensor Points (SP).
(Main
Menu)
(Selection
of
SP)
Activate
or
deactivate
SP
See
3.6.1
Define
gas
type
See
3.6.2
Define
measuring
range
See
3.6.3
Adjust
signal
form
of
the
transmitter
See
3.6.4
SP Mode
active
Gas Type
CO
SP Setup
SP 01
active
Measuring Range
250 ppm
SP Signal
linear