PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 20
3.7.5
System Time, System Date
Time and date have no memory back up; therefore after each power supply OFF-ON time and date restart.
Input and correction of time and date. Selection of the time and date format.
Symbol Description
Default
Status
Function
US
Time format US
EU = Display of time and date in EU format
US = Display of time and date in US format
hh.mm.ss Time
hh.mm.ss = Input of the correct time (EU format)
hh.mm.ss am = Input of the correct time (US format)
MM.DD.YY Date
MM.DD.YY = Input of the correct date (EU format)
MM.DD.YY = Input of the correct date (US format)
3.7.6
Customer Password (Code 1)
Change the system password for level 1
Symbol Description Default
Status
Function
1234
Customer
Password
1234
1234 = Define the customer’s password with 4 characters
3.7.7
Analog Output
The Single Point Gas Controller has one analog output (AO01) with (0)4 to 20 mA / (0)2 to 10 V signal. The signal of
SP01 or/and SP02 can be assigned to the analog output. The assignment is effected in the menu “SP Setups“ for
each SP. The sensor point sends the signal, which is defined in the menu “C/A Mode“.
The output signal (mA / V) and starting point (0 / 20%) is selected at the I/O Board by means of jumper. See fig. 5.
Out of the signals of all assigned measuring points the Single Point Gas Controller determines the minimum, the
maximum or the average value and transmits it to the analog output. The definition, which value is transmitted, is
effected in the menu “Analog Output 1“.
The analog output can be calibrated at 4 and at 20 mA, only in mA mode. Therefore an ampere meter (measuring
range 25 mA) can be attached to the AO and the respective factor has to be changed until the analog output
corresponds to 4 and/or 20 mA. During calibration evaluation of the sensor point signals is not possible. This
calibration is effected by the factory. The factors shall not be changed.
Symbol Description Default
Status
Function
Max.
Select
Output Mode Max.
Min. = Displays the minimum value of all assigned SP
Max. = Displays the maximum value of all assigned SP
Average = Displays the average value of all assigned SP
4.0
20.0
Calibration
4.0
20.0
4. = Calibration factor at 4 mA
20.0 = Calibration factor at 20 mA
3.7.8
Define the Failure Relay
Definition of the failure relay. See also fault management (3.1)
Symbol Description Default
Status
Function
0X
Fault Relay R0X
R0X = Define the fault relay