Single-Point Controller
User Manual - SPC3-11XX
Page 17
3.6.7
Control Mode
Definition of the alarm evaluation by means of current (CV) or average value (AV).
Symbol Description
Default
Status t Function
SP 01
Sensor Point
Selection of SP No.
CV Evaluation CV CV = Control by the current gas value
AV = Control by the average gas value
Current- average value function see: 3.7.4
3.6.8
SP Fault Assigned to Alarm
Definition, which alarms are activated in case of a fault at the measuring point.
Symbol Description
Default
Status
Function
SP 01
Measuring Point
Selection of SP No.
Alarm - 1 2 3 4
Fault - 0 0 0 0
Failure SP
0 0 0 0
0 = Alarm not ON at SP failure
1 = Alarm ON at SP failure
3.6.9
Alarm Assigned to Alarm Relay
Each of the 4 alarms can be assigned to any alarm relay. Unused alarms are not assigned to any alarm relay.
Symbol Description
Default
Status Function
SP 01
Measuring Point
Selection of SP No.
1
A1
A2
A3
A4
01
02
03
04
01 = Alarm 1 activates alarm relay R 01
02 = Alarm 2 activates alarm relay R 02
03 = Alarm 3 activates alarm relay R 03
00 = Alarm 4 doesn’t activate any alarm relay
3.6.10 SP Signal Assigned to Analog Output
The sensor point signal can be assigned to the analog output. At this the signal defined in the control mode (current or
average value) is transmitted.
Analog output see also: 3.7.7
Symbol Description
Default
Status Function
SP 01
Measuring Point
Selection of SP No.
0 A
0 0 = SP Signal not assigned to analog output
1 = SP Signal assigned to analog output 1