Single-Point Controller
User Manual - SPC3-11XX
Page 12
3.5.4
Horn Function
The internal horn is connected to alarm relay R3 (open collector).
This alarm output is defined as horn relay by this setup with the following possibilities to reset.
x
By pressing any of the 4 push-buttons (only possible in the starting menu).
x
Automatic reset at the end of the fixed time.
x
By an external push-button (assignment of the appropriate digital input).
The horn function is only activated if at least one of the two setups (time or digital input) is set.
Special function Response
After acknowledging the output (by push-button or externally) time starts. When this time has run out and the alarm is
still acting, the relay is set again.
Symbol Description Setting
Status Function
R 03
Relay No.
Selection of relay
Quit Mode
0
0 = Reset of
the relay after time having run out, or by push-button
1 = Reset of the relay by push-button, after time having run out and
when alarm is still acting, relay is set again. (Response function).
Time
120 Time for automatic reset function or response function
0 = no reset function
DI
0
Assignment, which digital input resets the output.
Acknowledge the horn output
Alarm 3
Relay 3
Gas concentration higher lower than threshold
Acknowledging
signal
On
Of
On
Off
On
Off
Time
Special function “Response“. (Return of the horn relay)
Alarm 3
Relay 3
Gas concentration higher lower than threshold
Acknowledging-
signal
On
Off
On
Off
On
Off
Time
Time