PolyGard
®
Single-Point Controller
User Manual - SPC3-11XX
Page 07
SP 02 < 3mA
Erased
Error still
exists
3.1
Fault Management
The integrated fault management records the last 15 faults with date and time stamps in the menu “System Errors.”
Additionally a record of the faults occurs in the “Error Memory”, which can be selected and reset only by the service
technician.
An actual fault is displayed in plain text in the starting menu. The failure relay, which is defined in the system setup
“Failure relay”, is activated. The yellow LED in the front of the gas controller flashes.
In case of fault of a sensor point (SP) the alarms defined in the menu “SP Setup” is activated additionally.
3.1.1 Acknowledge a Fault
Attention:
Acknowledging a fault is only possible after having removed the cause.
Select
menu
“System
Errors”
Example:
Failure
SP
01
<
3
mA
Reset
the
fault?
Fault
reset
Fault
reset
Cause
not
eliminated
Reset
not
possible
3.1.2 Error Memory
The menu “Error Memory“ in the main menu “System Error” can only be opened via code level 2.
In the error memory the last 15 faults are listed for the service technician even if they were already acknowledged in
the menu “System Error“. The deletion of each individual message is effected in the same way as the reset of a fault.
System Errors
SP 02 < 3mA
05.02 10.38
SP 02 < 3mA
Reset ??