2/4
C 10
Operating mode
G 03898 - Edition05 - August 12
Remote control via
RS232/RS485 connector
Remote control
operating modes
Remote control via
J14 remote control
connector
Pump alone
The pump is monitored by the equipment in which it is installed
(such as an automated pumping system or an industrial equipment).
The pump is remote controlled by the opening or closing of
different dry contacts wired on remote control connector (
B 70
).
This mode is enabled when
J14-S1
contact is open that also inhibit
the control of the pump by the HHR. However, the data and
operating parameters can be read on the HHR.
Pump alone or in a group of pumps
The pump is monitored by the equipment in which it is installed,
either alone or in a group of pumps.
The pump is remote controlled by the commands transmitted on the
serial link (refer to
B 110
for wiring and
C 90
for commands).
Pump control
mode
How enable the mode ?
Display
on HHR
How to
disable ?
Local mode
using HHR
Connect the HHR on the
connector.
Connect the remote control
cover plug on J14.
Press
CONT
key.
LOC
Press
CONTROL
key on
HHR.
Remote
control mode
via J14 remote
connector
Connect the pump to the
tool via J14 (
B 70
).
Open
S1
contact to remote
control the pump.
REM
Close
S1
contact on
J14.
Serial link
mode
via
RS232/485
connector
Connect the pump to the
tool via RS232/485 (
B 110
).
Send
CTRLON
command
(
C 90
).
RS
Send
CTRLOFF
com-
mand.
1 - RS
mode has priority on
LOC
and
REM
mode.
2 - REM
mode has priority on
LOC
mode.
3 - LOC
mode has NO priority on the other modes.
Pump control mode
Priority
adixen Vacuum Products - A3H Series Operating instructions