2/4
B 50
GB 02877 - Edition 04 - Januar
y 10
Electrical connection
Electrical connection
Electrical connection using a
plug (option)
0LUG
2EARPANEL
-AINPOWER
!!PUMPS
2EARPANEL
!PUMP
The pump is supplied with a plug separately packaged.
Plug type : female plug (6 co earth)
Connect the mains cable to the power supply plug using wire with the
following specification:
Cable (customer supply)
A103P
AWG-14 (or 2.08 mm
2
)
A603P / A1003P
AWG-10 (or 5.26 mm
2
)
Then, connect the power supply plug on the pump frame power supply
connector
and lock it
.
{
}
W
U
V
Earth
3
1
2
6
5
4
Not used
Main cable
Check that the cable is correctly protected against ground defects and that
earth wire is longer than the three conducting wires.
A603P pump model is not equipped with a frequency converter on the roots
Blower.
the motor rotation depends directly on the main power connection.
Uncorrect wiring may cause backwards pump rotating.
It is necessary to check the direction of rotation at first start up.
See
B 51.
adixen Vacuum Products - Operating instructions - A3P Series