2/2
B 01
A3P Series – Hook-up requirements
G 04345 - Edition 02 - Oct 13
Electricity
(B 50)
A103P
A603P
A1003P
Power consumption at maximum inlet
flow
2 kW
3 kW
Short Circuit Current Rating
of main electrical cabinet
5 kAIC
Power supply voltage -
Low voltage
200-230 V
Full load current 50 H
z
Full load current 60 H
z
Breaker
size
Cable
section
11.4 A
11.4 A
15 A
AWG-14 (2.5 mm
2
)
17.1 A
17.6 A
30 A
AWG-10 (4 mm
2
)
22.8 A
22.8 A
30 A
AWG-10 (4 mm
2
)
Power supply voltage -
High voltage
380-440 V
Full load current 50 H
Z
Full load current 60 H
Z
Breaker size
Cable
section
6 A
6 A
10 A
AWG-14 (2.5 mm
2
)
9.2 A
9.4 A
20 A
AWG-10 (4 mm
2
)
12 A
12 A
20 A
AWG-10 (4 mm
2
)
Pumping circuit
(B60)
A103P
A603P
A1003P
Gas inlet -
flange
DN 50 - ISO K
DN 100 - ISO K
material
remarks
Stainless Steel
a bellow is necessary
Gas exhaust -
flange
material
remarks
DN 25 - ISO KF
Stainless Steel
a bellow is necessary
Exhaustable enclosure
(B 60)
A103P
A603P
A1003P
Flow
Static
pressure*
Exhaust
22 cfm
0.125 wg
Ø 50 mm
* Measured at the secondary exhaust port.
For SEMI configuration, the main circuit breaker must be provided by
the end user and should have a minimum of 10 kAIC rating.
Electrical shock may result in severe injury.
Always disconnect main power before servicing the pump.