Pulscon LTC57 PROFIBUS PA
Diagnostics and troubleshooting
495
Diagnostics event
simulation
Deactivate simulation
C
Warning
497
Block output simulation Deactivate simulation
C
Warning
585
Simulation distance
Deactivate simulation
C
Warning
Diagnostic of process
801
Energy too low
Increase supply voltage
S
Warning
825
Operating temperature
1. Check ambient temperature
2. Check process temperature
S
Warning
825
Operating temperature
1. Check ambient temperature
2. Check process temperature
F
Alarm
921
Change of reference
1. Check reference configuration
2. Check pressure
3. Check sensor
S
Warning
936
EMC interference
Check installation on EMC
F
Alarm
941
Echo lost
Check DC value
F
Alarm
a
942
In safety distance
1. Check level
2. Check safety distance
3. Reset self holding
S
Alarm
b
943
In blocking distance
Reduced accuracy
Check level
S
Warning
944
Level range
Reduced accuracy
Level at process connection
S
Warning
950
Advanced diagnostic 1
to 2 occurred
Maintain your diagnostic event
M
Warning
c
Table 11.8
a
Diagnostic status is changeable.
b
Diagnostic status is changeable.
c
Diagnostic status is changeable.
Diagnostic
number
Short text
Repairing action
Status signal
(from the
factory)
Diagnostic
behavior
(from the
factory)