Pulscon LTC57 PROFIBUS PA
Integration into a PROFIBUS network
2015
-0
3
65
9
Integration into a PROFIBUS network
9.1
Overview of the device database files (GSD)
9.2
Set device address
Figure 9.1
Address switches in terminal compartment
9.2.1
Hardware adressing
Setting hardware addressing
1. Set switch 8 to
OFF
.
2. Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts
automatically.
Figure 9.2
Example of hardware addressing: switch 8 is in position
OFF
; switches 1 to 7 define
the address.
Manufacturer ID
93 (5D HEX)
Ident number
0E3B HEX
Profil version
3.02
GSD file
Information and files under:
• www.pepperl-fuchs.com
• www.profibus.org
GSD file version
Table 9.1
2
98
3
4
5
6
7
8
1
DI
P
ON
Switch
1
2
3
4
5
6
7
Value in position
ON
1
2
4
8
16
32
64
Value in position
OFF
0
0
0
0
0
0
0
Table 9.2
2
98
3
4
5
6
7
8
1
DIP
ON
2 + 8 = 10