Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
109
Fail safe type
Fail safe value
Blocking
Navigation
Expert
Analog inputs
Analog input 1 to 6
Fail safe type
Description
Standard parameter
FSAFE_TYPE
of the Analog Input Block according to the
PROFIBUS profile.
Selection
• Fail safe value
• Fallback value
• Off
Factory setting
Off
Additional information
Meaning of the options
This parameter specifies the output value of the Analog Input Block in the event of
an error.
•
Fail safe value
The output value in the event of an error is defined in the
Fail safe value
parameter (page 109).
•
Fallback value
The last output value that was valid before the error occurred is retained.
•
Off
The output value follows the current measured value. The status is set to BAD.
Blocking
Navigation
Expert
Analog inputs
Analog input 1 to 6
Fail safe value
Prerequisite
Fail safe type
(page 109) =
Fail safe value
Description
Standard parameter
FSAFE_VALUE
of the Analog Input Block according to the
PROFIBUS profile.
User entry
Signed floating-point number
Factory setting
0
Additional information
This parameter defines the output value of the Analog Input Block in case of an
error.